Inspect surrounding area for combustibles, advise owner & relocate combustibles - Inspect general condition of the system (signs of water, burnt wires & damage)
- Check for appropriate supply of fresh air into room
- Check the overall performance of the system while the system is in operation
- Listen for odd sounds while unit is in operation
- Check for accumulation of dirt or rust on the vent pipe or vent hood collection area
- Vent pipe must be inspected for rust, holes, sagging & signs of damage. Check & seal flue at chimney
- All flue pipe joints must be screwed at three places to avoid disconnecting at the joints
- Test low water cut off
- Flush all of the boiler drains & low water cut off
- Remove the pig tail & flush out
- Test pressure troll (lift switch with screwdriver to test)
- Check glass gauge for damage, flush & clean (mark water height 1” from top)
- Ring out all safety devices (check with ohm meter)
- Check operation of emergency switches
- Check for gas leaks
- Check the color of the flames for good Air/Gas mixture
- Burners must be inspected for rust, dirt & signs of damage
- Make sure burners are relocked in their slots and seated on the burner orifices
- Check gas pressure (on the burner side of the gas valve)
- Vacuum burner box (wire brush if necessary)
-
Check & tighten all electrical connections including locknuts & connectors
Read more about why maintenance is important. Schedule maintenance service online now or call us at 973-227-3599.